MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE - 100.0 AMPERES AC ALL LOCATIONS OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS - 500.0 AC ALL LOCATIONS FREQUENCY IN HERTZ - 60.0 ALL LOCATIONS CIRCUIT PROTECTION TYPE - OVERCURRENT ALL LOCATIONS TRIP RELEASE METHOD - THERMAL-MAGNETIC ALL LOCATIONS TRIP RELEASE AMBIENT TEMP RATING - 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS TRIP RELEASE CHARACTERISTIC - INSTANTANEOUS AND TIME DELAY ALL LOCATIONS TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT - 3600.000 NOMINAL AT 150 PCT AND 420.000 MINIMUM AT 200 PCT AND 1500.000 MAXIMUM AT 200 PCT AND 120.000 MINIMUM AT 300 PCT AND 240.000 MAXIMUM AT 300 PCT ALL LOCATIONS ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT - 175.0 ALL LOCATIONS BODY STYLE - 1D RECTANGULAR DIMENSIONAL ENVELOPE OVERALL LENGTH - 4.594 INCHES NOMINAL OVERALL HEIGHT - 3.531 INCHES NOMINAL OVERALL WIDTH - 3.844 INCHES NOMINAL MOUNTING FACILITY TYPE AND QUANTITY - 6 TERMINAL TERMINAL TYPE AND QUANTITY - 6 SCREW FEATURES PROVIDED - ADJUSTABLE TRIP RELEASE ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS - 1200.0 TO 1400.0 AC ALL LOCATIONS DESIGN CONTROL REFERENCE - ETN4376 (We do not proofread any ads submitted by members) |
theodorecase@desmoines-classifieds.com (Theodore Case)
for more information. Your emails will be instantly forwarded to the poster's private address.